Manifacturer | Autonics |
Display method | 4-digit 11-segment LCD |
Control method | ON/OFF control, P, PI, PD, PID control |
Input specification | Thermocouple: K(CA), J(IC), T(CC), R(PR), S(PR), L(IC) |
RTD: DPt100Ω, Cu50Ω | |
Sampling cycle | 50ms |
Control output | Current (DC0/4-20mA) or SSR drive (13VDC )[ON/OFF] |
Option output | Alarm 1 |
Power supply | 100-240VAC~ 50/60Hz |
Protection structure | IP50(front panel) |
Display accuracy_RTD | •At room temperature(23℃±5℃):(PV ±0.3% or ±1℃, select the higher one) ±1-digit |
•Out of room temperature:(PV ±0.5% or ±2℃, select the higher one) ±1-digit | |
Display accuracy_Thermocouple | •At room temperature(23℃±5℃):(PV ±0.3% or ±1℃, select the higher one) ±1-digit |
•Out of room temperature:(PV ±0.5% or ±2℃, select the higher one) ±1-digit | |
Hysteresis(adjustable sensitivity) | 1 to 100℃/℉(0.1 to 50.0℃/℉) variable |
Proportional band | 0.1 to 999.9℃/℉ |
Integral time | 0 to 9999 sec |