Ambient/Storage Temperature | 0…50 ºC / -25…60 ºC |
Relative Humidity | 80% relative humidity temperatures up to 31 °C, decreasing linearly to 50% at 40 °C |
Protection Degree | According to EN 60529 IP20 |
Height | Max. 2000m |
Supply | 90-250V AC, 50/60Hz, 7VA |
Input Signal | 0/4-20mA, 0/1-5V DC, 0/2-10V DC or 1kΩ ~ 10kΩ potentiometer (device may be damaged at ±12V DC and above voltages) |
Transmission Signal | >0.2mA (mA for input), >0.08V (V for input) |
Drop-out Signal | <0.18mA (mA for input),<0.075V (V for input) |
Turn-on Time | 15ms |
Protection | Available against cross-connection of input signal |
Dynamic Input Impedance | <100ohm (mA for input), >10kohm (V for input) |
Insulation Voltage | 2500 Vrms 1 minute between input and output terminals |
External Connections | Screw-terminals |
Load Current, AC51/25°C (Arms) | 4A AC |
Load Voltage (Vrms) | 180-280 |
Overload Current t=1s/25°C (Arms) | 150 |
Nonrecurrent Surge Current/25°C (Arms) | 400 |
Voltage Drop in Transmission (Vrms) | 1.6 |
Leakage Current (mArms) | 5 |
I²t Value for Fuse t=10ms (A²s) | 880 |
Frequency (Hz) (Hz) | 50-60 |
Power Factor (CosØ) | >0.75 |
Minimum Operating Current (mArms) | 160 |
Control Type | Phase angle controlled by using adjustment knob or 0-10V DC analog input signal |
Mounting Method | Wall mounting |
Dimensions | W80xH160xD55 mm |
Weight | Approx. 350g (After packing) |
Enclosure Material | Self extinguishing plastics |
Enda, Solid State Relay, Solid State Relay
ERFA1-240F
- 40A AC load current
- 280V AC load voltage
- 0/4-20mA, 0/1-5V DC, 0/2-10V DC or 1kohm to 10kohm potentiometer input
- 4 digits display
- 24V DC auxiliary power supply
- Phase angel or zero-cross controlled
- Soft Start or Kick Start functions
- Varistor protection for peak voltages
- CE marked according to European Norms