Ambient/Storage Temperature | 0…50 ºC / -25…70 ºC |
Relative Humidity | 80% Relative humidity for temperatures up to 31 °C, decreasing linearly to 50% at 40 °C |
Protection Degree | According to EN 60529 Front panel:IP65, Rear panel:IP20 |
Height | Max. 2000m |
Electrical Characteristics | |
Supply | 230/110V AC +10% -20% or 12/24V AC ±10%, 50/60Hz or 9-30V DC / 7-24V AC ±10% SMPS |
Power Consumption | 7VA |
External Connections | Screw-terminals |
Scale | Adjustable between -1999…4000 |
Accuracy | 0-1V DC: ±0.5% (of full scale) |
0-10V DC: ±0.5% (of full scale) | |
0-20mA DC: ±0.5% (of full scale) | |
4-20mA DC: ±0.5% (of full scale) | |
Measurement Range | 0-1V DC: Max. 1.1V |
0-10V DC: Max. 12V | |
0-20mA DC: Max. 25mA | |
4-20mA DC: Max. 25mA | |
Input Empedance | 0-1V DC: Approx. 100kohm |
0-10V DC: Approx. 100kohm | |
0-20mA DC: Approx. 10ohm | |
4-20mA DC: Approx. 10ohm | |
Outputs | |
Auxiliary Power Supply | All sensor supply outputs maximum 50 mA (regulated and isolated) |
Alarm Output | 2 Relays: 250V AC, 8A (for resistive load), NO |
Life Expectancy | Mechanical 30.000.000 operations (under no load), Electrical 100.000 operations (8A at 250V AC, resistive load) |
Control | |
Control Type | Double set-point and alarm control |
Control Algorithm | On-Off |
Hysteresis | Adjustable between 1…200 |
Housing | |
Mounting Method | Panel mounting |
Dimensions | W77xH35xD61 mm |
Weight | Approx. 250g (after packaging) |
Enclosure Material | Self extinguishing plastics |
Enda, Temperature & Process Controllers, Temperature & Process Controllers
EI2041-SM
4 digits display |
Display scale can be adjusted between -1999 and 4000 |
Decimal point can be adjusted between 1. and 3. digits |
Measurement unit can be displayed |
Selectable four different standard input types (0-20mA, 4-20mA, 0-1V, 0-10V) |
User can calibrate the device according to specified input type |
Sampling time can be adjusted in four steps |
Stores maximum and minimum measurement values |
Two relay outputs for control and alarm (order option) |
Above and below set point value can be set |
Selectable independent, deviation and band alarm |
Sensor supply output(Optional) |
RS485 Modbus RTU communication protocol feature (order option) |
CE marked according to European Norms |