ERAA2-440Z-F


  • 2×25 and 2x40A AC load current
  • 280V AC or 480V AC load voltage
  • 90-240V AC input voltage
  • LED status indicator for input voltage
  • Zero-cross switching
  • Applicable for three phase loads
  • Built-in varistor protection
  • CE marked according to European Norm

Ambient/Storage Temperature -25…60 ÂșC / -30…100 ÂșC
Relative Humidity 90% relative humidity for temperatures up to 2°C, decreasing linearly to 50% at 4°C
Protection Degree According to EN 60529 IP20
Height Max. 1000m
Input Voltage 90-240V AC
Pick-up Voltage >75V AC
Drop-out Voltage ˂6V AC
Input Current ˂8mA AC
Turn-on Time Max. 1 Period
Turn-off Time Max. 2 Period
LED Indicator If the input voltage ˃75V AC then LED lits
Load Current (Arms) ERAA2-225Z: 2×25
ERAA2-240Z-F: 2×40
ERAA2-425Z: 2×25
ERAA2-440Z-F: 2×40
Load Voltage (Vrms) ERAA2-225Z and ERAA2-240Z-F: 24-280
ERAA2-425Z and ERAA2-440Z-F 50-480
Frequency (Hz) 50-60
Mounting Method TH35 rail mounting
Dimensions ERAA2-225Z and ERAA2-425Z: W46xH100xD117 mm
ERAA2-240Z-F and ERAA2-440Z-F: W46xH110xD117 mm
Weight ERAA2-225Z and ERAA2-425Z: 475g (after packaging)
ERAA2-240Z-F and ERAA2-440Z-F: 500g (after packaging)
Enclosure Material Self extinguishing plastics
SKU: ERAA2-440Z-F Categories: , ,

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “ERAA2-440Z-F”

There are no reviews yet.